Configuring the hardware
2024-04-16Last updated
To enable Security Center to monitor and manage the output relays and readers connected to your Axis Powered by Genetec unit, you must configure them within the Hardware subpage of the Powered by Genetec page.
Before you begin
- Connect the readers to your Axis Powered by Genetec unit, and make a note of which port
each reader is connected to.
Each Axis Powered by Genetec unit has one (A1210) or two (A1610) reader ports. Each port can be connected to either one Wiegand reader or up to two OSDP readers. The readers are set to OSDP by default.
- Be sure to write down the following information for OSDP readers:
- Baud rate (9600, 19200, 38400, or 115200).
Must be the same for all readers connected to the same port.
- Physical address (0 - 126).
- Encryption key (32 hexadecimal characters), if applicable.
- Baud rate (9600, 19200, 38400, or 115200).
- Be sure to restart the device if you have configured auxiliary I/Os as outputs in the AXIS device interface.