2025-01-08Last updated
The Axis Powered by Genetec device connects directly to the Security Center Access
Manager role. From the perspective of the Access Manager, the Axis Powered by Genetec device is
an access control unit.
Security Center 5.11.3 and later supports the following Axis
Powered by Genetec devices. Note: Each Axis Powered by Genetec device must have the following
firmware packages installed:
- The Synergis™ Softwire app, called firmware in Security Center.
- The Axis firmware (AXIS OS), called platform in Security Center.
For compatibility information, see
Product compatibility for access control on the Genetec TechDoc
Hub.
Model |
Description |
A1210, A1210-B |
Axis Powered by Genetec one-door controller.
- 1 Wiegand or 2 OSDP readers
- 6 inputs and 1 tamper input for each configured OSDP reader
- 1 output relay
- 2 auxiliary I/Os (can be configured as inputs or outputs)
- Up to 250,000 cardholders (credentials) – On-premises Security Center
- Up to 40,000 cardholders (credentials) – Security Center SaaS Edition
(Classic)
- Up to 40,000 cardholders (credentials) – Security Center SaaS
- Up to 150,000 offline events
- Up to 1,000 connections to the Access Manager (standalone server)
- Dimensions: 144 x 122 x 50 mm (5.7 x 4.8 x 2.0 in)
- Power in: 12 V DC or PoE+ (IEEE 802.3at)
- Certifications and standards1
|
A1610, A1610-B |
Axis Powered by Genetec two-door controller.
- 2 Wiegand or 4 OSDP readers
- 8 inputs and 1 tamper input for each configured OSDP reader
- 2 output relays
- 4 auxiliary I/Os (can be configured as inputs or outputs)
- Up to 250,000 cardholders (credentials) – On-premises Security Center
- Up to 40,000 cardholders (credentials) – Security Center SaaS Edition
(Classic)
- Up to 40,000 cardholders (credentials) – Security Center SaaS
- Up to 150,000 offline events
- Up to 1,000 connections to the Access Manager (standalone server)
- Dimensions: 175 x 175 x 60 mm (6.9 x 6.9 x 2.4 in)
- Power in: 12 V DC or PoE+ (IEEE 802.3at)
- Certifications and standards2
|
1 Approvals: EAC, EN 55035, EN 55032 Class B, EN 50130-4, EN 61000-3-2,
EN 61000-3-3, FCC Part 15 Subpart B Class A, ICES-003 Class A, VCCI Class A, RCM AS/NZS
CISPR 32 Class A, KC KN32 Class B, KC KN35. Safety: IEC/EN/UL 62368-1, UL 294, UL 2043.
Environment: NEMA TS 2 (2.2.7-2.2.9), IEC 60068-2-1, IEC 60068-2-2, IEC 60068-2-6, IEC
60068-2-14, IEC 60068-2-27, IEC 60068-2-78. Others: CSA C22.2 No.
205-1983.
2 Approvals: EN 55032 Class A, EN 50130–4, EN 61000-3-2, EN
61000-3-3, EN 55024, EN 61000-6-1, EN 61000-6-2, FCC Part 15 Subpart B Class A, ICES-003
Class A, VCCI Class A, RCM AS/NZS CISPR 32 Class A, KC KN32 Class A, KC KN35. Safety:
IEC/EN/UL 62368-1, UL 2043, UL 294, UL 293. Environment: EN 50581. Others: CSA C22.2 No.
205-1983.